Duracell Inverter 3000 Guía de instalación Pagina 22

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 37
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 21
Operating Limits
975-0444-01-01 3–3
Operating Limits
Power Output
The Duracell Inverter 3000 can deliver up to 2500 W continuous and up
to 3000 W for five minutes.
Input Voltage
The allowable inverter input (battery) voltage ranges are shown in the
following table:
Operating Condition Voltage Range Comment
Normal 10.5–15 V
Optimum
Performance
12.0–13.0 V
Low Voltage Alarm 11.0 V or less The audible low battery alarm
sounds.
Low Voltage
Shutdown
less than 10.5 V
The inverter shuts down to protect the
battery from being over-discharged.
High Voltage
Shutdown
15 V or more The inverter shuts down to protect
itself from excessive input voltage.
Note: Although the inverter
incorporates over-voltage protection,
it can still be damaged if input
voltage exceeds 16 V.
Dur_Inverter_3000_Owners_Guide.book Page 3 Tuesday, June 3, 2008 11:51 AM
Vista de pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 36 37

Comentarios a estos manuales

Sin comentarios